Typical rooftop installation![]() |
Interior View![]() |
| Model | FD400 | FD500 | |
| Motor-Variable Speed | Voltage | 220-240 | 220-240 |
| Watts-Model TACEVA | 2x750W | 2x1000w | |
| Amp Draw low/high | 2.7/3.85 | 2.9/5.6 | |
| RPM low/high | 600-750/1350 | 850-1410 | |
| Fan | Auswing II 40o | X | |
| Powerflow Fixed Pitch | X | ||
| Pump - Quietflo | 35 LPM | 2x | 2x |
| Filter Media - Celdek Flute size 7050/45 |
Number of Pads | 6 | 6 |
| Size mm | 2x795Hx928W 4x795Hx645W |
2x960Hx928W 4x960Hx645W |
|
| Density mm | 100 | 100 | |
| Cooling Capacity m3 (Comcool zone 2) |
960 | 1200 | |
| Design Air Flow | m3/hr | 28 000 | 36 000 |
| cfm | 16 500 | 21 300 | |
| Lit/sec | 7 800 | 10 000 | |
| Dropper Duct Size | 1165x585 | 1165x585 | |
| Depth/Width mm | 1630x1200 | 1630x1200 | |
| Height mm | 995 | 1160 | |
| Height above Dropper mm | 745 | 910 | |
| Operating mass kg | 102 | 114 | |